Product Details:

Place of Origin Anhui, China (Mainland)
Brand Name Land

Payment & Shipping Terms:

Payment Terms: L/C,T/T

Detailed Product Description


The Application of Cable

It is used in places with high demand on flame-proof such as high-rise building, oilfield, power station, mine, subway, control & supervision loop and computor system. Through development & application of oxygen-seperation technology, a kind of colloid inorganic metallic compound which is nontoxic, smell-less and without halogen is hilled between insulation and outer sheath. When the cable is burning, the original soft metallic compund heated and discomposed, released the eduction of crystallized water, absorbed much heat, thus reducing the temperature of outer combustible and surrounding environment. That makes the burning cable self-extinct

The Description

i. Executive Standard:  As enterprise's standard and GB12666-90

ii. Working Condition

   1. Rated A.C. voltage: U0/U ( V series: 600/1000v, K series: 450/750v, B series: 450/750v)

   2. Max. long term working temperature

       a. flame-retardant PE insulation & sheath: 70oC&105oC, XLPE insulation: 90oC

       b. fluoroplastic insulation & sheath: 200oC & 260oC, fluoroplastic insulation: 105oC, flame-retardant PE & sheath : 90oC& 125oC

       c. low smoke&halogen, PVC insulation & sheath: 70oC, low smoke & halogen, flame-retardant polyolefin insulation & sheath: 90oC &125oC

   3. Min.environment temperature:

       a. flame-retardant PVC insulation & sheath: -40oC for fixed installation and -15oC for non-fixed installation

       b. fluoroplastic insulation & sheath: -60oC for fixed installation and -20oC for non-fixed installation.

   4. Installation temperature for cable should be no lower than 0oC.

   5. Flame-retardant character:

                                              GB 12666.5-90           cable characters

       flame-supplying time            40 min                         40 min

       self-burning time                  ≤1h                             8 min

       burning length(qualified)        ≤2.5m                         1.1 m

    6. Allowed bending radius recommended for installation:

        cable with braided shield & without armor should be no less than 6 times that of cable outer diameter

        cable with steel-tape armor should be  no less than 12 times than that of cable outer diameter

        cable with fluoroplastic insulation & sheath should be no less than 8 times than that of cable outer diameter.

Flame-retardant Cable with Oxygen-separation Layer Flame-retardant Cable with Oxygen-separation Layer

Send your message to this supplier
« Prev Product ... 15 16 17 18 19 20 21 ... Next Product »

Other Products from this Supplier

Company Info

Anhui Land Group Co., Ltd.
[China (Mainland)]
[Verified Member]

City: Chuzhou
Province/State: Anhui
Country/Region : China (Mainland)

Business Type:Manufacturer, Trading Company

View Contact Details

Email this page Bookmark this page Print this Page